Offline config, Message timeout-loss of communications – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 380

Transferring Program Files
21–7
7.
The screen displays a series of status messages while the program file is being
transferred. When the transfer is complete the system prompts you to confirm
reading the program. Press
CONFIG
OFFLINE
CONFIG
YES
F8
. The screen displays the program
directory menu for
EXAMPLE
.
Press a key, enter file number or file name
REM PROG
L532 Series C Rev.2
PROC Addr 1
PROGRAM DIRECTORY FOR PROCESSOR: EXAMPLE
FILE
PROTECTED
NAME
TYPE
SIZE (words)
0
system
74
1
reserved
0
2
ladder
8714
F1
F2
F6
F7
F3
F4
F8
PROCSSR
FUNCTNS
SAVE
RESTORE
CREATE
REPORTS
FILE
OPTIONS
RETURN
TO MENU
CHANGE
LNK ADR
MONITOR
FILE
F9
F10
DATA
MONITOR
MEMORY
MAP
8.
Save
EXAMPLE
to disk on this APS terminal by pressing
CONFIG
OFFLINE
CONFIG
SAVE
RESTORE
F2
and then
CONFIG
OFFLINE
CONFIG
SAVE
PROGRAM
F2
. Confirm your selection by pressing
CONFIG
OFFLINE
CONFIG
YES
F8
. Node 0, the
sending APS terminal, downloads program file EXAMPLE to node 3, the
receiving APS terminal.
Note
Do not exit the Transfer Completed display at node 0 yet. Exiting at this point
causes a
Message Timeout-Loss of Communications
critical error in
the receiving APS terminal.
Press any key to return to the program directory menu and press
CONFIG
OFFLINE
CONFIG
RETURN
TO MENU
F3
.
This completes the receiving procedure at node 3. Return to node 0, the sending
APS terminal.
At node 0, the sending APS terminal, the screen displays
TRANSFER
COMPLETE
.