Configuring Your Programming Device for Online Communication

11–11

1784-KT (DH

+

Bridged) and 1784-KT2 (DH

+

Bridged) Interface Cards

The 1784-KT (DH

+

Bridged) or the 1784-KT2 (DH

+

Bridged) interface cards

require a 1785-KA5 DH

+

/DH-485 gateway module to bridge the DH

+

and DH-485

data links when communicating from a terminal located on a DH

+

data link.

Current Device

1784-KT (DH+ Bridged)

F3

Connection

DIRECT

F4

Terminal DH

+

Address

0 (octal)

F5

SLC Node Address

1 (decimal)

F6

KA5 DH

+

Address

1 (octal)

F7

IRQ

3

F8

Board Address

000011

F9

Save to File

F9

Press a function key

SAVE T0

FILE

F5

F6

SLC

ADDRESS

KA5

ADDRESS

F3

CONNECT

TYPE

F2

SELECT

DEVICE

F4

TERM

ADDRESS

ESC exits/Alt-U aborts changes

ONLINE CONFIGURATION

F7

IRQ

F8

BOARD

ADDRESS

Function Key

Description

[F2] Select Device

Toggles between the selected interface card and the interface

card selection menu.

[F3] Connect Type

Toggles between Direct and MultiĆDrop. Direct means that the

terminal has a termination resistor (last device on the DH

+

link). MultiĆDrop means that the terminal does not have a

termination resistor. The default is Direct.

[F4] Terminal Address

Allows you to select a terminal address on DH+ as a node

number from 0–77 octal. The default is 0.

[F5] SLC Address

Allows you to select a processor address on DHĆ485 as a

node number from 1–31 decimal. The default is 1.

[F6] KA5 Address

Allows you to select a KA5 address on DH

+

as a node number

from 0–77 octal. The default is 1.

[F7] IRQ

Allows you to select the IRQ on the board (3, 4, 5, and 7.) The

software default is 3. This selection must match the setting of

the jumpers on your KT(2) card (hardware default is 0). See

the KT(2) card user manual for details..