Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 408

Advertising
background image

Preface

Advanced Programmming Software User Manual

A–14

Display Message

Recommended Action

Description

KF3 ADDRESS CANNOT EQUAL

PROCESSOR ADDRESS

The 1770ĆKF3 and processor are at the

same node address.

Change their node addresses to be

unique.

LINK ERROR

Unrecognized or unknown problem with

the communication driver.

Retry the function. If you still have

problems contact your RSI

representative.

LOSS OF MODEM CARRIER

While online with DF1 Full Duplex

through a 1770ĆKF3 and a modem, a

disconnection or hangup occurred.

Retry the function.

LOSS OF MODEM DSR STATUS

While online with DF1 Full Duplex

through a 1770ĆKF3, the modem went

inactive.

Check the connection and retry the

function.

M0/M1 ADDRESS MONITORING ONLY

SUPPORTED ONLINE

An attempt to monitor an M0/M1 file was

made using a processor other than an

SLC 5/03.

Change the processor to an SLC 5/03;

go online with APS; retry M0/M1 address

monitoring.

M0/M1 ADDRESS MONITORING

CURRENTLY DISABLED

M0/M1 address monitoring is disabled in

the APS configuration.

Enable M0/M1 address monitoring and

retry the function.

M0/M1 ADDRESSES CANNOT BE

MODIFIED

Unable to modify M0/M1 addresses from

the M0/M1 data table monitor.

Informational message. You cannot

modify M0 and M1 files from the data

table monitor.

MAXIMUM COMMUNICATION DRIVER

SIZE EXCEEDED

The link layer driver is too large to fit into

the memory available.

Verify the size, date, and time for the link

layer file. Also run CHKDSK" from the

DOS prompt.

MAXIMUM NODE ADDRESS

VIOLATION DETECTED

The software detected a device at a

node higher than the current maximum

node address.

Change the Max. Node Address in the

online Configuration screen.

MESSAGE TIMEOUTS - LOSS OF

COMMUNICATIONS

Either 1) the specified device is currently

busy; 2) the requested device is not at

the specified address; 3) the requested

device is not at the specified baud rate;

4) the PC may not be able to

communicate through the requested port

at the selected baud rate; or 5) electrical

noise exists in the network wiring.

1) Verify all addresses and baud rates;

2) verify that the SLC has power and

that it is sufficient to run the processor;

3) check the power supply jumper on the

processor, verify positioning for the

current input power; 4) use the Who

function to determine network

configuration; or 5) correct noise

problem.

MODULE MUST BE SPECIFIED

BEFORE SPECIAL CONFIG.

The Special I/O function key was

pressed while the highlighted slot was

empty.

Specify module and retry function.

MULTIPOINT ADDRESSES MUST

ALREADY EXIST

An attempt to add an address to the

multiĆpoint list was made, but failed

since the address does not currently

exist in the program.

Specify the address in the program and

then retry the function.

Advertising