Preface
Advanced Programming Software User Manual
19–10
1.
Access the Force menu functions, by pressing
CONFIG
OFFLINE
CONFIG
FORCE
F9
.
2.
Place the cursor on the output instruction and press
[F2]
ON
to install the force
ON. (Press
F1 OFF
to install a force OFF.)
MicroLogix 1000 controllers only: Since forces are always enabled, skip step 3.
3.
Enable the forces by pressing
CONFIG
OFFLINE
CONFIG
ENABLE
F7
. Confirm your selection. The
following display appears:
Press a key for desired forcing function
(file 2, rung 3)
REM RUN
forces ENABLED
PROC Addr 1
F2
ON
F3
REMOVE
F7
F8
ENABLE
DISABLE
F10
MONITOR
OUTPUTS
F9
MONITOR
INPUTS
F1
OFF
ON
F4
REMOVE
ALL
( )
O:0.0
0
END
( )
B3
10
( )
B3
11
] [
B3
11
]/[
B3
12
]/[
B3
10
] [
I:0.0
1
( )
B3
12
] [
B3
11
] [
I:0.0
1
]/[
B3
10
] [
I:0.0
1
] [
B3
11
For the previous display, the following is now true:
•
Output O:0/0 is forced on and enabled; however, it is not intensified because it
is not logically true.
•
The controller’s output LED is on.
•
The controller’s Forced I/O LED is on continuously.