Configuring Your Processor for Online Communication

13–15

DF1 Full-Duplex Channel 0 Configuration

When the system mode driver is a DF1 Full-Duplex for channel 0 the following
screen is displayed:

Communication Driver:

DF1 FULL-DUPLEX

Diagnostic File:

Reserved

Baud Rate:

1200

Parity:

NONE

Stop Bits:

1

Duplicate Detect:

ENABLED

Error Detect:

CRC

ACK Timeout [20 ms]:

2

NAK Retries:

3

Source ID:

9

ENQ Retries:

3

Control Line:

NO HANDSHAKING

Embedded Responses:

ENABLED

F2

UNDO

EDITS

Press a key for desired function

REM PROG

no forces

EDITS: NONE

PROC Addr 1

Channel 0 System Mode Configuration

F1

ACCEPT

EDITS

F9

CHAN

STATUS

F10

SELECT

OPTION

You can configure the DF1 Full-Duplex driver even if the Current Communication
Mode of channel 0 is set to User.

Parameter

Description

Diagnostic File

Reserved for future use.

Baud Rate

Toggles between the communication rate of 110, 300, 600, 1200, 2400,

4800, 9600, and 19200. The default is 1200.

Parity

Toggle between None and Even. The default is None.

Stop Bits

Toggles between 1, 1.5, and 2. The default is 1.

Duplicate Packet

Detection

Toggles between Disabled and Enabled. The default is Enabled.

Error Detection

Toggles between CRC and BCC. The default is CRC.

ACK Timeout

Valid range is 2-65535 (in 20 ms increment) The default is 50.

NAK Retries

Valid range is 0-255. The default is 3.

ENQ Retries

Valid range is 0-255. The default is 3.

Control Line

Toggles between No Handshaking and FullĆDuplex modem. The default is

No Handshaking.

Embedded

Responses

Toggles between Enabled and AutoĆDetect. The default is Enabled.

Source ID

Specify the address of the sender in this field. Valid range is 0-254. The

default is 9.