Offline config, Press, The following display appears – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 219

Configuring Your Programming Device for Online Communication
11–25
2.
Press
CONFIG
OFFLINE
CONFIG
HALF
DUPLEX
F10
. The following display appears:
F9
Press a function key
SAVE TO
FILE
F1
Master Poll Timeout
(x20 ms)
50
F2
Message Retries
3
F3
RTS Send Delay
(x20 ms)
0
F4
RTS Off Delay
(x20 ms)
0
F5
Command Reply Timeout
(X55 ms)
198
F6
Pre-send Time Delay [x1 ms]
0
F7
Stop Bits
1
F9
Save to File
Half Duplex Configuration
F3
SEND
DELAY
F5
REPLY
TIMEOUT
ESC exits/Alt-U aborts changes
F1
POLL
TIMEOUT
F2
MESSAGE
RETRIES
F4
OFF
DELAY
F6
PRESEND
DELAY
F7
STOP
BITS
Function Key
Description
[F1] Poll Timeout
Allows you to select the master poll timeout value in
increments of 20 ms. The valid range is 0–65,635. The
default is 50.
[F2] Message Retries
Allows you to select the message retries value. The valid
range is 0–255. The default is 3.
[F3] RTS Send Delay
Allows you to select the RTS send delay value in increments of
20 ms. The valid range is 0–65,535. The default is 0.
[F4] Off Delay
Allows you to select the RTS off delay value in increments of
20 ms. The valid range is 0–65,535. The default is 0.
[F5] Reply Timeout
Allows you to select the reply timeout value in increments of
55 ms. The valid range is 18–25,000. The default is 198.
[F6] PreĆsend Time Delay
Allows you to select a preĆsend time delay in increments of
1 ms. The valid range is 0-65,535. The default is 0.
[F7] Stop Bits
Toggles between 1 and 2. The default is 1.
[F9] Save to File
Saves the halfĆduplex slave parameters to the user file.