Configuring Your Programming Device for Online Communication

11–25

2.

Press

CONFIG

OFFLINE

CONFIG

HALF

DUPLEX

F10

. The following display appears:

F9

Press a function key

SAVE TO

FILE

F1

Master Poll Timeout

(x20 ms)

50

F2

Message Retries

3

F3

RTS Send Delay

(x20 ms)

0

F4

RTS Off Delay

(x20 ms)

0

F5

Command Reply Timeout

(X55 ms)

198

F6

Pre-send Time Delay [x1 ms]

0

F7

Stop Bits

1

F9

Save to File

Half Duplex Configuration

F3

SEND

DELAY

F5

REPLY

TIMEOUT

ESC exits/Alt-U aborts changes

F1

POLL

TIMEOUT

F2

MESSAGE

RETRIES

F4

OFF

DELAY

F6

PRESEND

DELAY

F7

STOP

BITS

Function Key

Description

[F1] Poll Timeout

Allows you to select the master poll timeout value in

increments of 20 ms. The valid range is 0–65,635. The

default is 50.

[F2] Message Retries

Allows you to select the message retries value. The valid

range is 0–255. The default is 3.

[F3] RTS Send Delay

Allows you to select the RTS send delay value in increments of

20 ms. The valid range is 0–65,535. The default is 0.

[F4] Off Delay

Allows you to select the RTS off delay value in increments of

20 ms. The valid range is 0–65,535. The default is 0.

[F5] Reply Timeout

Allows you to select the reply timeout value in increments of

55 ms. The valid range is 18–25,000. The default is 198.

[F6] PreĆsend Time Delay

Allows you to select a preĆsend time delay in increments of

1 ms. The valid range is 0-65,535. The default is 0.

[F7] Stop Bits

Toggles between 1 and 2. The default is 1.

[F9] Save to File

Saves the halfĆduplex slave parameters to the user file.