Configuring Your Programming Device for Online Communication

11–35

Example Configuration: DH+ to DH-485 via 1785-KA5 Gateway

SLC 5/03 processor

Node 7

(octal)

APS 6.0 or later

Node 77

(octal)

Node 2

(octal)

CH0

Node 1

(octal)

DH+

Link ID=1

57,600 baud

DHĆ485

Link ID=2

19,200 baud

KA5

Current Device

1784-KT (DH+ Bridged)

F1

Bridge Type

DH+ to DH485 via 1785 KA5 Gateway

Terminal Name
Terminal Address

77 (octal)

Baud Rate

57600

F5

Remote SLC Node Addr.

1 (decimal)

F6

KA5 DH+ Address

7 (octal)

F7

KA5 DH485 Link ID

2 (decimal)

IRQ

5

Board/Memory Address

001011

F8

Curr. Interchange Port

1

F9

Save to File

F9

Press a function key

SAVE TO

FILE

ESC exits/Alt-U aborts changes

ONLINE CONFIGURATION

F8

NEXT

PORT

F5

REMOTE

ADDRESS

F2

SELECT

DEVICE

F1

SELECT

BRIDGE

F6

KA5 DH+

ADDRESS

F7

KA5 485

LINK ID

Function Key

Description

[F1] Select Bridge Type

Allows you to select the desired bridge type: DH+ to DH+ via

two 1785ĆKA, DH+ to DH485 via 1785 KA5 Gateway, PI

routing, or DH+ to Channel 0 via 5/04 passthru.

[F2] Select Device

Toggles between the selected device driver and the device

driver selection menu.

[F5] Remote SLC Node Address

Allows you to enter the SLC address. Valid range is 1–31

decimal. The default is 1.

[F6] KA5 DH+ Address

Allows you to enter the KA5 DH+ address. Valid range is 0–77

octal. The default is 7.

[F7] KA5 DHĆ485 Link ID

Allows you to enter the KA5 DH+ link ID. Valid range is 0–15

decimal. The default is 2.

[F8] Next Port

Allows you to select the port number where the interface card

is installed. Valid range is 1–8. The default is 1.

[F9] Save to File

Saves the selected parameters to a user file.