Remote program mode (all processors) – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 284

Advertising
background image

Changing Processor Modes

15–3

The following table details the different modes available to the SLC 5/03 and SLC
5/04 processors:

Keyswitch Position

Processor Mode

Status Line

RUN

Run

RUN

REMOTE

Run

Program

Test Ć Single Step

Test Ć Single Scan

Test Ć Continuous Scan

REM RUN

REM PROG

REM SRG

REM SSN

REM CSN

RUN

Run or Suspend

SUSP

REMOTE

Run, Test, or Suspend

REM SUSP

not applicable

Faulted

FAULT xxxx

PROG

Program

PROG

If you are online with an SLC 5/03 or SLC 5/04 processor and the keyswitch
position is in RUN and you press the clear major fault function key, the
processor enters the Run mode once you clear the fault.

You cannot restore a file from disk to the processor until the processor is placed in
either the PROGram, REMote Program, or Fault mode. (The keyswitch is not in the
RUN position.)

REMote Program Mode (All Processors)

The REMote Program mode facilitates the transfer of processor files through the
restore function. In this mode the processor does not scan or execute the ladder
program, and all outputs are de-energized. When the processor is in this mode it
functions as if the keyswitch were in the PROGram position.

The remote program mode allows you to:

Monitor the ladder program in the processor (without rung state indication).

Set up I/O forces.

Save a processor file to disk.

Use the search function.

Monitor and edit data files.

Transfer processor files to and from a memory module. (Does not apply to
MicroLogix 1000 controllers.)

Perform SLC 5/03 and SLC 5/04 online edits.