Saving and Compiling a Processor File

9–3

The following figure shows the displays for all other available processors.

File Name:

EXAMPLE

F6 Future Access:

ALLOW

ESC exits

File Name:

EXAMPLE

F1 Single Step Test

DISABLE

F3 Index Across Files:

DISALLOW

F4 File Protection

OUTPUTS

F6 Future Access:

ALLOW

ESC exits

File Name:

EXAMPLE

F6 Future Access:

ALLOW

File Protection:

NONE

F7 Adjustable Filters

ESC exits

SLC 5/02 Processor

Fixed or SLC 5/01 Processor

MicroLogix 1000 Controller

Function Key

Description

[F1] Single Step Test - SLC 5/02

processor

(For SLC 5/03 and SLC 5/04

processors this feature is always

enabled.)

Toggles between Enable and Disable. This option allows you

to execute your program one rung at a time or a section at a

time. Use this function for debugging purposes. See page

9-4 for more information.

[F3] Index Checks - SLC 5/02,

SLC 5/03, SLC 5/04 processors

Toggles between Allow and Disallow. This option allows you

to use indexed addressing to address data table elements

outside of the base address data file. See page 9-4 for more

information.

[F4] File Protect - SLC 5/02

processor

(For SLC 5/03 and SLC 5/04 File

Protection see chapter 8.)

Toggles between Outputs, None, and All. This option allows

you to protect your data table files from external modification

by devices on the DHĆ485 network. See page 9-5 for more

information.

[F5] Force Protect - SLC 5/03

and SLC 5/04 processors

Toggles between Enable and Disable. This option allows you

to prevent I/O forces from being enabled. This protection

takes effect only after the processor file is downloaded to a

controller. See page 9-5 for more information.

[F6] Future Access - Fixed,

SLC 5/01, SLC 5/02, SLC 5/03,

and SLC 5/04 processors, and

MicroLogix 1000 controllers

Toggles between Allow and Disallow. This option allows you

to protect proprietary program algorithms. The protection

takes effect only after the processor file is downloaded to a

controller. See page 9-5 for more information.

[F7] Adjustable Filters -

MicroLogix 1000 controllers

Allows you to select input filter response times at the time your

program is developed. See page 9-6 for more information.