Configuring slc 5/01 and slc 5/02 processors, 13œ2, Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 252: Node address, Baud rate

Advertising
background image

Preface

Advanced Programming Software User Manual

13–2

Configuring SLC 5/01 and SLC 5/02 Processors

APS versions 2.0 and later support DH-485 point-to-point communication. You can
connect APS to the SLC 500 processors using a 1747-PIC Interface Converter, a
1770-KF3 module, or 1747-KE module. A 1747-AIC Link Coupler is required for
DH-485 network communication.

APS

SLC 500

Modular I/O Controller

1747–PIC

Interface Converter

The parameters that must be configured for online communication are explained
below.

Note

The SLC 5/01 and SLC 5/02 processors store their node addresses and baud rates in
word S:15. We recommend making these parameters part of your user program.
This prevents unauthorized (or unintended) alteration of your program. Refer to the
system status file in the
Instruction Set Reference Manual for more information
about word S:15.

Node Address

Each device on the DH-485 network must have a unique node address. The default
node address for APS is 0, and the default for the processors is 1. To change a
processor node address, write a value between 1 and 31 using the Who function.
The change is applied immediately.

Baud Rate

Each DH-485 network device must have a common baud rate. The table below
shows the available baud rates. You must cycle power to apply the new baud rate.

Processor

Baud Rate

Fixed and SLC 5/01

9600 or 19200

SLC 5/02

1200, 2400, 9600, or 19200

Advertising