Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 264

Advertising
background image

Preface

Advanced Programming Software User Manual

13–14

Parameter

Description

Diagnostic File

Reserved for future use.

Baud Rate

Toggles between the communication rate of 110, 300, 600, 1200,

2400, 4800, 9600, and 19200.

Parity

Toggles between None and Even. The default is None.

Stop Bits

Toggles between 1, 1.5, and 2. The default is 1.

Station Address

The valid range is 0-254 decimal. The default is 1.

Duplicate Packet Detection

Toggles between Enabled and Disabled. The default is Enabled.

Error Detection

Toggles between CRC and BCC. The default is CRC.

ACK Timeout

Allows you to select the ACK timeout value in increments of 20 ms.

The valid range is 0-65535.

RTS Off Delay

Allows you to select the RTS off delay value in increments of

20 ms. The valid range is 0-65535. The default is 0.

Message Retries

Allows you to select the message retries value. The valid range is

0-255. The default is 3.

RTS Send Delay

Allows you to select the RTS send delay value in increments of

20 ms. The valid range is 0-65535. The default is 0.

PreĆsend Time Delay

Allows you to select the RTS preĆtransmit time delay in increments

of 20 ms. The valid range is 0-65535.

Control Line

Toggles between No Handshaking, FullĆDuplex Modem, and

HalfĆDuplex Without Continuous Carrier.

Polling Mode

Toggles between Message Based (Do Not Allow Slave to Initiate

Messages), Message Based (Allow Slave to Initiate Messages),

Standard (Single Message Transfer Per Node Scan), and Standard

(Multiple Message Transfer Per Node Scan).

Priority Polling - Low

Allows you to select the Priority Polling Range Low Address. The

valid range is 0-255.

Normal Polling - Low

Allows you to select the Normal Polling Range Low Address. The

valid range is 0-255.

Priority Polling - High

Allows you to select the Priority Polling Range High Address. The

valid range is 0-254.

Normal Polling - High

Allows you to select the Normal Polling Range High Address. The

valid range is 0-254.

Reply Message Wait Time

Allows you to select the Reply Message Wait Time setting in

increments of 20 ms. The valid range is 0-65535.

Normal Poll Group Size

Allows you to select the Normal Poll Group Size. The valid range

is 0-255.