The edit fields menu, 18œ5, Offline config – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 350

The Multi-Point Function
18–5
The Edit Fields Menu
From the multi-point list menu, you can access the edit fields menu by pressing
CONFIG
OFFLINE
CONFIG
EDIT
F1
FIELDS
. The following function keys are available:
Press a function key
REM PROG
no forces
EDITS: NONE
PROC Addr 1
F10
EXIT
F3
TOGGLE
STATE
F5
F8
EDIT
OFF DSC
DELETE
ENTRY
F1
EDIT
ADDRESS
F2
DEFINE
SYMBOL
F4
EDIT
ON DESC
F7
FORCE
These keys perform the following functions:
Function Key
Description
[F1] Edit Address
Allows you to update the address in the highlighted field
(unless the entry is protected). The address must be a direct
bit address that currently exists in the program. It may be
entered either as a logical address or as a symbol, provided
the symbol has already been defined in the documentation
database.
[F2] Define Symbol
Allows you to define or edit the symbol for the highlighted
address.
[F3] Toggle State
Toggles the state in the data table of the bit that is addressed
by the current entry. This does not effect any force applied to
the bit.
[F4] Edit ON Description
Allows you to enter an ON description for the current entry (up
to 16 characters in length). This description is displayed when
the bit's state is either 1, 1FON, or FON.
[F5] Edit OFF Description
Allows you to enter an OFF description for the current entry
(up to 16 characters in length). This description is displayed
when the bit's state is either 0, 0FOF, or FOF.
[F7] Force
Allows you to access the multiĆpoint force menu. See page
[F8] Delete Entry
Removes the highlighted entry from the multiĆpoint list (unless
the entry is protected).
[F10] Exit
Exits the edit fields menu and returns you to the multiĆpoint list
menu.