Configuring Your Programming Device for Online Communication

11–39

Example Configuration: DF1 Full-Duplex to DH+ via 5/04 Passthru

DF1 to DH+ bridging is allowed via an SLC 5/04 OS401 processor when the
passthru bit is enabled. An example is shown below.

Processor B

SLC 5/04 processor

CH1

Node 23

(octal)

APS 6.0 or later

Node 77

(octal)

CH0

Node 2

(octal)

CH1

Node 14

(octal)

DF1 FullĆDuplex

Link ID=2

19,200 baud

DH+

Link ID=1

57,600 baud

Processor A

SLC 5/04 OS401 processor

S:34/5=1

To program the SLC 5/04 OS401 processors on DH+, use the DF1 full-duplex
driver
. As shown in the screens that follow, enter the destination address 19 decimal
for processor A, and enter the destination address 12 decimal for processor B.

F1

Port

COM1

Current Device

Full-Duplex

F4

Source Address

0

F5

Destination Address

19

F7

Device/Modem/Full-Duplex Configuration

F9

Save to File

F9

Press a function key

SAVE TO

FILE

F1

PORT

F2

SELECT

DEVICE

ESC exits/Alt-U aborts changes

ONLINE CONFIGURATION

F7

DEVICE

CONFIG

F4

SOURCE

ADDRESS

F5

DEST

ADDRESS

Screen for Processor A