Preface

Advanced Programming Software User Manual

20–8

4.

Once you select the file, press

CONFIG

OFFLINE

CONFIG

CONVERT

TO HEX

F1

. The menu functions allow you to

select the size of the PROM.

SLC 5/01 and SLC 5/02 processors

8K bytes corresponds to Allen-Bradley modules specifying 1K
instruction words (1747- M1, M3)

32K bytes corresponds to Allen-Bradley modules specifying 4K
instruction words (1747-M2, M4)

SLC 5/03 processors

OS300 – 64K bytes or 128K bytes

OS301 – 64K bytes or 128K bytes

OS302 – 64K bytes, 128K bytes, or 256K bytes

SLC 5/04 processors

OS400 – 128K bytes

OS401 – 128K bytes or 256K bytes

When you create hexadecimal files for the SLC 5/03 and SLC 5/04 processor,
you have the option of setting the memory module protect byte. After you
select the number of bytes, the message:

Set Memory Module

Protection

is displayed.

5.

If you want to apply protection (permanently burn your memory module), press

CONFIG

OFFLINE

CONFIG

WRITE

PROTECT

F8

Otherwise, press

CONFIG

OFFLINE

CONFIG

ALLOW

REUSE

F10

. Then confirm your selection by

pressing

CONFIG

OFFLINE

CONFIG

YES

F8

. Refer to chapter 8 for more information on protecting

your program files.