Configuring Your Processor for Online Communication

13–11

DH-485 Master Channel 0 Configuration

When the system mode driver for channel 0 or channel 1 is DH-485 Master, the
following screen is displayed:

Communication Driver:

DH-485

Diagnostic File:

Reserved

Baud Rate:

19200

Node Address:

1

Max Node Address:

31

Token Hold Factor (1–4):

1

F2

UNDO

EDITS

Press a key for desired status function

REM PROG

no forces

EDITS: NONE

PROC Addr 1

Channel 0 System Mode Configuration

F1

ACCEPT

EDITS

F9

CHAN

STATUS

F10

SELECT

OPTION

Separate channel configurations exist for channel 0 and channel 1 DH-485 Master
configurations. You can configure channel 0 even if the current communication
mode is set to User.

Parameter

Description

Diagnostic File

Reserved for future use.

Baud Rate

Toggles between the communication rate of 1200, 2400, 9600, and 19200.

The default is 19200.

Node Address

This is the node address of the processor on the DHĆ485 network. The

valid range is 1-31. The default is 1.

Max Node Address

This is the maximum node address of an active processor. The valid range

is 1-31. The default is 31.

Token Hold Factor

Determines the number of transactions allowed to make each DHĆ485 token

rotation. Increasing this value allows your processor to increase its DHĆ485

throughput. This also decreases throughput to others on the DHĆ485 link.

The valid range is 1-4. The default is 1. SLC 5/01 and 5/02 processors are

factory set to 1.