Configuring Your Programming Device for Online Communication

11–31

Example Configuration

The following 1784-KT parameters are read from the cfg_kt.ini file.

Current Device

1784-KT (DH+ Direct)

Connection

DIRECT

Terminal Name

MYKT

Terminal Address

0 (octal)

Baud Rate

57600

F5

SLC Node Address

3 (octal)

IRQ

3

Board/Memory Address

110011

F8

Curr. Interchange Port

1

F9

Save to File

F9

Press a function key

SAVE TO

FILE

ESC exits/Alt-U aborts changes

ONLINE CONFIGURATION

F8

NEXT

PORT

F5

PROC

ADDRESS

F2

SELECT

DEVICE

Function Key

Description

[F2] Select Device

Toggles between the selected device driver and the device

driver selection menu.

[F5] Processor Address

Allows you to select a processor address as a node number.

Valid range is 0–77 octal. The default is 1.

[F8] Next Port

Allows you to select the port number where the interface card

is installed. Valid range is 1–8. The default is 1.

[F9] Save to File

Saves the selected parameters to a user file.