Preface

Advanced Programming Software User Manual

9–6

Allow: Online access to the processor file and data table is unrestricted. This is the
default.

Disallow: Online access to the processor program is not permitted. You cannot:

monitor the program or create reports

enter or change the password

save the online processor file to disk

transfer the file from the processor memory to a memory module (SLC 500
processors only)

However, you can:

edit or view user data

clear the processor memory

create the processor configuration and data table reports (SLC 500 processors
only)

transfer the contents of a memory module into the processor memory (SLC 500
processors only)

restore (download) a different program to the controller

Note

If you lose or delete the offline copy of the program, you cannot access the program
in the controller. You must clear the controller memory and re-enter the program.

This feature is not recommended for use when the HHT is your only source of
program backup.

There is no “back door” access to get around this feature. If you intend to use this
feature, back up your program.

[F7] Adjustable Filters (MicroLogix 1000 Controllers)

This option allows you to select input filter response times for the 1761–L16BWA
and 1761–L32BWA micro controllers.

Note

The input filter response times can only be adjusted at the time your program is
developed.

The input filter response time is the time from when the external input voltage
reaches an on or off state to when the micro controller recognizes that change of
state. The higher you set the response time, the longer it takes for the input state
change to reach the micro controller. However, setting higher response times also
provides better filtering of high frequency noise.