Forcing an external output circuit, 19œ9 – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 360

Advertising
background image

The Force Function

19–9

Forcing an External Output Circuit

A forced external output circuit is independent of the internal logic of the ladder
program and the output data file. Installing forces on output circuits affects only the
output force table. Installed, enabled forces do not affect the output data file or the
program logic. However, they do affect the output circuit. The effects of installed
and enabled forces can only be seen in the Run mode. The Test mode does not
energize output circuits.

The following figure is an example online Monitor File display for processor file.
The status line indicates that the processor is in the Run mode and no forces exist.
The cursor is located on instruction O:0/0 in rung 3.

Press a function key
(file 2, rung 3)
REM RUN

no forces

PROC Addr 1

F2

CONFIG

DISPLAY

F3

EXIT

F6

F7

SEARCH

GENERAL

UTILITY

F9

FORCE

F8

DATA

MONITOR

F1

CHANGE

MODE

( )

O:0

0

END

( )

B3

10

( )

B3

11

] [

B3

11

]/[

B3

12

]/[

B3

10

] [

I:0

1

( )

B3

12

] [

B3

11

] [

I:0

1

]/[

B3

10

] [

I:0

1

] [

B3

11

The procedure for forcing external output circuits is the same as forcing external
input data file bits. For your reference the procedure follows. Refer to pages 19–3
and 19–4 for menu displays.

Advertising