Offline config – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 201

Advertising
background image

Configuring Your Programming Device for Online Communication

11–7

Note

When using the serial port with APS, COM1 must use IRQ 4 and COM2 must use
IRQ 3.

Once you select the 1747-PIC Interface Converter the following addresses must be
set:

Terminal Node Addresses

The DH-485 network requires you to set unique node addresses for the terminal and
each processor or other devices on the network. This section describes how to set
the node address for the APS terminal and the default APS processor. The default
APS processor address is the node the APS terminal attempts to establish
communication with when you go online.

Setting APS Terminal Node Address: The default node address for an APS terminal
is 0. To change the terminal address, do the following:

1.

Press

CONFIG

OFFLINE

CONFIG

TERM

ADDRESS

F4

.

2.

Type any number between 0 and 31.

3.

Press

[ENTER]

.

Note

The terminal address cannot equal the processor address.

Setting Default APS Processor Addresses: The address of the processor APS will try
to communicate with when you attempt to go online from the main menu. To
change the processor address, do the following:

1.

Press

CONFIG

OFFLINE

CONFIG

PROC

ADDRESS

F5

.

2.

Type any number between 1 and 31.

3.

Press

[ENTER]

.