Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 262

Preface
Advanced Programming Software User Manual
13–12
DF1 Half-Duplex Slave Channel 0 Configuration
When the system mode driver is DF1 Half-Duplex Slave for channel 0 the following
screen is displayed:
Communication Driver:
DF1 HALF-DUPLEX SLAVE
Diagnostic File:
Reserved
Baud Rate:
1200
Parity:
NONE
Stop Bits:
1
Station Address:
0
Duplicate Detect:
ENABLED
Error Detect:
CRC
RTS Off Delay [x20 ms]:
0
RTS Send Delay [x20 ms]:
0
Poll Timeout [x20 ms]:
50
Pre-send Time Delay [x1 ms]: 65535
Message Retries:
0
Control Line:
NO HANDSHAKING
EOT Suppression:
NO
F2
UNDO
EDITS
Press a key for desired status function
REM PROG
no forces
EDITS: NONE
PROC Addr 1
Channel 0 System Mode Configuration
F1
ACCEPT
EDITS
F9
CHANNEL
STATUS
F10
SELECT
OPTION
You can configure the DF1 Half-Duplex Slave driver even if the Current
Communication Mode of channel 0 is set to User.
Parameter
Description
Diagnostic File
Reserved for future use.
Baud Rate
Toggles between the communication rate of 110, 300, 600, 1200,
2400, 4800, 9600, and 19200. The default is 1200.
Parity
Toggles between None and Even. The default is None.
Stop Bits
Toggles between 1, 1.5, and 2. The default is 1.
Station Address
The valid range is 0-254 decimal. The default is 1.
Duplicate Packet Detection
Toggles between Enabled and Disabled. The default is Enabled.
Error Detection
Toggles between CRC and BCC. The default is CRC.
RTS Off Delay
Allows you to select the RTS off delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
RTS Send Delay
Allows you to select the RTS send delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
Poll Timeout
Allows you to select the master poll timeout value in increments of
20 ms. The default is 50. The valid range is 0-65535.
PreĆsend Time Delay
Allows you to select the RTS preĆtransmit time delay in increments
of 20 ms. The valid range is 0-65535.