background image

APS Error Messages

A–11

Display Message

Recommended Action

Description

FILE, RUNG, END MCR IS ONLY

ALLOWABLE INSTRUCTION ON RUNG

Rungs containing `end MCR' cannot

contain any other instructions on that

rung. During a program save or test

edits a rung was detected that violates

this rule.

Configure the address for the given

processor and resave the program.

FILE, RUNG, INDEXED O, I, & S

ADDRESSES CURRENTLY ILLEGAL

During program save or test edits, an

indexed input, output, or status file

address was detected where these files

are not allowed.

Change any indexed O, I, S addresses.

FILE, RUNG, SYNTAX ERROR

During program save or test edits a rung

was detected to contain invalid

instruction codes or rung structure.

Contact your RSI representative.

FILENAME MUST BE SPECIFIED

A file name has not been specified.

Specify a file name.

FORCE STATE CANNOT BE MODIFIED

DUE TO FILE FORCE PROTECTION

An attempt was made to force

input/output files that are protected.

Go offline, deselect force protection,

then restore the program.

FUNCTION DISALLOWED

This message could mean either 1) you

are not the program owner; 2) the file is

not open for read/write; or 3) the

directory is currently open.

Retry the function.

I/O CONFIGURATION DOES NOT

MATCH PROGRAM

The user program contains references to

unconfigured I/O addresses.

Change the addresses or reconfigure

the I/O.

I/O CONFIGURATION FILES CANNOT

BE MODIFIED DURING ONLINE

EDITING

I/O configuration files cannot be

modified while in the online editing

session.

Go offline and edit; then restore the

program.

ILLEGAL DATA OR PARAMETER

VALUE

The value input is not valid.

1) Check the file number, the file type,

the count, and address being used; 2)

use the WHO function to verify that the

processor maximum node address is

31.

ILLEGAL FILE TYPE

During configuration of report options for

the cross reference report an illegal

starting or ending file type was entered.

Enter a valid file type and retry the

function.

ILLEGAL PROGRAM ACCESS

ATTEMPTED

An invalid password was entered for a

password protected file.

Enter a valid password for the specified

file.

ILLEGAL SELECTĆTHE I" RUNG

ATTACHED TO THE SELECTED R"

RUNG CANNOT BE FOUND

During an attempt to perform a

cut/copy/paste, the first rung selected

was marked for replacement.

Contact your local Rockwell Software

representative.

ILLEGAL SIZE

An Ext STS error occurred during

communications indicating an illegally

sized communication packet.

Verify that the bridge device is properly

configured.