3 Digital I/O Specifications

3.4.6 32-point Output Modules

3-98

2) Module Type Setting

The type of Output Module mounted in the slot is set as the Module type. Only the
last 11 alphanumeric characters of the model number are necessary. For example
120DDO35410 is the Module type for the JAMSC-120DDO35410.

3) I/O Reference Number Setting

(a) The leading I/O reference number used by the Output Module is set.

(b) Any one of the I/O reference numbers and points listed in the following table

can be set.

(c) When an output coil is set, the leading I/O reference number must satisfy the

following equation:

Leading reference number of I/O coil = 000001 + 16 n

where n = 0 to 63 for the CPU20 and

n = 0 to 255 for the CPU30

For example, 000001 can be set as the leading reference number, but
000002 cannot.

4) I/O Data Format

The following items can be set to define the I/O data format. There is, however, gen-
erally no need to change these settings because the default settings can be used
for most normal applications.

a) Bit Order

I/O can be processed by handling data either in ascending or descending order of
the bits. This is explained next for allocation of both output coils and output regis-
ters.

(1) When 32-point output coils are allocated from 000001, the bit order can be set

to either “MSB” or “LSB,” as described in the following table and shown in the
illustration below it. Allocation is performed in units of 16 output points.

Refer to Fig. 3.11 Allocation of Output Coils for details.

Type of Output

References for I/O Allocation

Points/Registers

CPU10, CPU20, CPU21

CPU30, CPU35

Output coils

000001 to 001024

000001 to 004096

32 points

Output registers

400001 to 400512

400001 to 400512

2 registers

Output Coil MSB Setting

The leading output reference number (000001) is allocated to the
smallest output number of the first 16 output points (output 1) on the
Output Module. The next output reference number (000017) is allo-
cated to the smallest output number of the second 16 output points
(output 17) on the Output Module.

Output Coil LSB Setting

The leading output reference number (000001) is allocated to the
largest output number of the first 16 output points (output 16) on the
Output Module. The next output reference number (000017) is allo-
cated to the largest output number of the second 16 output points
(output 32) on the Output Module.