3 Digital I/O Specifications

3.5.4 I/O Allocations

3-116

7) Setting the Timeout Output (Only for Digital Output Modules)

Make sure that the Parameter Setting Screen (I/O Map Module Editor) is being dis-
played.

(1) Move the cursor to TIMEOUT OUT and press the Enter Key to access the tim-

eout output setting.

(2) A screen will appear so that the timeout output setting can be selected.

Move the cursor to either FINAL DATA or SET VALUE and press the Enter
Key to select the desired timeout output status. If FINAL DATA is selected, the
data just before the CPU Module entered STOP status will be sent for all out-
puts until the CPU Module returns to RUN status.

The MEMOSOFT is set by default to SET VALUE.

The timeout output setting is only for Digital Output Modules, but not for Digital Input
Modules.

Fig. 3.33 Parameter Setting Screen: Time out Output

Fig. 3.34 Timeout Output Status Selection