6.4 Precautions on Wiring

6-47

6

3) Maximum Load Current for 12/24-VDC 16-point Output Modules

Although a 0.5-A load can be connected to each output point for the DC 16-point
Output Module, the total load must be 1.0 A or less for each of the four output points in
the same area marked by the shaded portion in the following figure. Keep the load
distribution within the 1.0-A limit.

If this limit is exceeded, damage may occur to the output circuit.

Fig. 6.28 Maximum Load Current for 16-point Output Modules

CAUTION

12 VDC
(24 VDC)

1.0 A/4 points

Fuse

-Common 1

+Common 1

Output 1

Output 2

Output 3

Output 4

Output 5

Output 6

Output 7

Output 8

Loads

Loads

0.5 A/point