3 Digital I/O Specifications

3.1.2 200-VAC 16-point Input Module

3-8

3) The following diagram shows an example of terminal connections.

Connect power supplies of the same phase to the Common 1 and Common 2.

If power supplies of different phases are connected, overheating or fire may
occur.

Note: (1) Crimp Terminals

Use M3 terminal for crimping to the terminal block.

(2) Recommended Wires

Use wires of 1.3 mm

2

(AWG16) to 0.5mm

2

(AWG20) to connect to the terminal

block.

(3) Terminal 10 and terminal 20 are not connected.

Input 1

Input 2

Input 3

Input 4

Input 5

Input 6

Input 7

Input 8

Common 1

Not connected.

Input 9

Input 10

Input 11

Input 12

Input 13

Input 14

Input 15

Input 16

Common 2

Not connected.

200 VAC

Terminals

EXAMPLE

CAUTION