3.1 Digital Input Module specifications

3-3

3

2) The following diagram shows the circuit configuration.

Connect power supplies of the same phase to the Common 1 and Common 2.

If power supplies of different phases are connected, overheating or fire may
occur.

Maximum Heating Value

2.0 W

Hot Swapping
(Removal/insertion under power)

Permitted

Approx. Mass

250 g

External Dimensions

40.3

×130×103.9 mm (W×H×D)

Item

Specifications

Input 1

Input 8

Common 1

Input 9

Input 16

Common 2

100 VAC

100 VAC

Input signal
indicator

To CPU

Photocoupler

Internal circuits