6.4 Precautions on Wiring

6-33

6

Although the capacity of surge absorber must be adjusted to the load, the following
surge absorber is recommended for general applications:

• CR50500 (manufactured by Okaya Electric Industries Co., Ltd.) or equivalent

Fig. 6.9 Connecting Inductive Loads

3) Long Wiring Runs from Input Devices

When long wiring is required for connection to external devices or when a large
induced voltage is generated due to a nearby inductive source, a dummy resistor
should be connected in parallel with the AC Input Module to suppress the induced
voltage.

If the dummy resistor is not connected, the input signal may become unstable and
malfunction will occur.

Although the size of dummy resistor must be adjusted to the inductive voltage, the
following surge values are recommended for general applications:

• At 100 VAC: 5k

Ω (10W min.)

• At 200VAC: 10k

Ω (20W min.)

Fig. 6.10 Long Wiring Runs from Input Devices

100 VAC
(200 VAC)

Surge absorber

Inductive load

Input

Input

Common

100 VAC
(200 VAC)

Long distance

Dummy resistor

Input

Input

Common