3 wiring dc i/o modules, 3) i/o signal cables, 4) protective fuses – Yaskawa 120 Series I/O Modules User Manual

Page 244: 1) dc power supply specifications, Caution

Advertising
background image

6.2 Panel Wiring

6-17

6

3) I/O Signal Cables

Do not allow foreign matter such as cable chips in the Modules or Mounting Bases.

Foreign matter in the Modules or Mounting Bases may cause fire, failures and/
or malfunctions.

a) There are five types of AC I/O Modules. See Table 6.5.  

To connect these I/O Modules to signal line, use I/O signal cable of the size listed in
Table 6.5. The cables differ in their permissible current capacity depending on the
conditions of use, such as the ambient operating temperature, so check the condi-
tions of use and select a cable of appropriate size.

b) M3 Phillips screws are used in the external connection terminals. Accordingly, use

crimp terminals for M3 Phillips screws for the Module-end of I/O signal cable.

4) Protective Fuses

If using an Output Module, connect a fuse that complies with the load specifications in
series with the load.

• 100/200-VAC 8-point Output Module: Model No. JAMSC-120DAO83000

• 100/200-VAC 16-point Output Module: Model No. JAMSC-120DAO84300

• Relay Contact 16-point Output Module: Model No. JAMSC-120DRA84300

If a fuse is not connected, a fire or damage to the device or output circuit may occur if
the load is short-circuited or the circuit overloaded.

6.2.3

Wiring DC I/O Modules

This section explains how to connect a power supply cable and an I/O signal cable
to a DC I/O Module.

1) DC Power Supply Specifications

a) As shown in Examples 1 and 2 later in this section, it is necessary to supply external

DC power (12/24VDC) to the DC I/O Modules listed in the following table to power
input signals and drive loads.

CAUTION

Table 6.5 I/O Signal Cable Size

Name

Model No.

I/O Signal Cable Size

100-VAC 16-point Input Module

JAMSC-120DAI54300

0.5 mm

2

(AWG20) to 1.3 mm

2

(AWG16)

200-VAC 16-point Input Module

JAMSC-120DAI74300

100/200-VAC 8-point Output Module

JAMSC-120DAO83000

100/200-VAC 16-point Output Module

JAMSC-120DAO84300

0.5 mm

2

(AWG20) to 1.3 mm

2

(AWG16)
Common cable: 1.3 mm

2

(AWG16) or larger

Relay Contact 16-point Output Module

JAMSC-120DRA84300

AC loads:
0.5 mm

2

(AWG20) to 1.3 mm

2

(AWG16)
Common cable: 1.3 mm

2

(AWG16) or larger

CAUTION

Advertising