4.2 Analog Output Specifications

4-33

4

4) The following diagram shows an example for terminal connections.

Note: (1) All the channels of the output circuit are isolated each other.

(2) Recommended Cables

Use shielded twisted-pair wires of 1.3 mm

2

(AWG16) to 0.5 mm

2

(AWG20) to

connect to the terminal block.

(3) One-point Shield Connection

As a rule, connect the shield at one point on the load side. However, better out-
put characteristics may be obtained by connecting it at one point on the Module
side rather than on the load side, so consider which way is better depending on
the actual situation. An incorrect connection will make input signal unstable and
cause malfunction.

(4) Grounding the Module

The “Not connected” terminals of the Module are not connected inside the Mod-
ule. Use them as relay terminals, if necessary.

(5) Crimp Terminals

Use M3 terminals for crimping to the terminal block.

(6) Unconnected Terminals

Terminals 1 to 5, 7, 9 to 13, 15 and 17 to 20 are not connected.

Not connected

External device

External device

4 to 20mA

4 to 20mA

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

CH2 -

Not connected

Not connected

Not connected

Not connected

Not connected

CH2 +

CH1 -

CH1 +

Shielded twisted-pair wire

Shielded twisted-pair wire

EXAMPLE

Advertising