4 Analog I/O Specifications

4.2.2 Analog Output Modules (0 to 10 V, 2 channels) (0 to 5 V, 2 channels)

4-26

2) Output Characteristics

The following diagram shows the output characteristics.

a) Output characteristics for 0 to 10 V, 2CH

b) Output characteristics for 0 to 5 V, 2CH

Note: (1) For 0 to 10 V (2 channels), an output register value exceeding

the range of 0 to 4000 will be clamped at 0 or 10.0 V.

(2) For 0 to 5 V (2 channels), an output register value exceeding the

range of 0 to 4000 will be clamped at 0 or 5.0 V.

Output register value

Analog output value

±2000 mode

0-4000 mode

≤0000

0.00 V

0.00 V

+1000

+2.50 V

+1.25 V

+2000

+5.00 V

+2.50 V

+3000

+7.50 V

+3.75 V

≥+4000

+10.00 V

+5.00 V

Analog output value(V)

Output register value

Analog output value(V)

Output register value