7.1 Built-in Fuses

7-3

7

7.1.2

Built-in Fuses

1) AC 16-point Output Modules

Do not replace the built-in fuses of the AC 16-point Output Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved
technician, a failure or a malfunction may occur in the AC 16-point Output Mod-
ules, and the guarantee is void.

a) The fuse inside an AC 16-point Output Module is not to protect the output circuit.

The fuse prevents the Module from damage that may occur in the following cases:

• External causes: For example, when over-voltage is applied to the power termi-

nals for driving load of the AC 16-point Output Module.

• Internal causes: For example, when foreign matter such as chips are present in

the AC 16-point Output Module, and thereby short-circuiting the
internal circuits.

b) When the built-in fuses are blown out, the indicator lamp “F” of the AC 16-point Out-

put Module is lit. If the fuses are blown out, eliminate the cause and replace the
Module with a spare AC 16-point Output Module.

2) DC 8-point Output Modules

Do not replace the built-in fuses of the DC 8-point Output Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved
technician, a failure or malfunction may occur in the DC 8-point Output Mod-
ules, and the guarantee is void.

a) The fuse inside a DC 8-point Output Module is not to protect the output circuit. The

fuse prevents the Module from damage that may occur in the following cases:

• External causes: For example, when over-voltage is applied to the power termi-

nals for driving load of the DC 8-point Output Module.

• Internal causes: For example, when foreign matter such as chips are present in

the DC 8-point Output Module, and thereby short-circuiting the
internal circuits.

b) Neither the fuse blowout detecting circuit nor indication lamp is provided in the DC 8-

point Output Modules.

If the output current does not flow though the rated voltage is applied to the DC 8-
point Output Module and the output signal indicator lamp is lit, the built-in fuse may
be blown out. If the fuse is blown out, eliminate the cause and replace the Module
with a spare DC 8-point Output Module.