Caution – Yaskawa 120 Series I/O Modules User Manual

Page 55

Advertising
background image

3.2 Digital Output Module Specifications

3-25

3

2) The following diagram shows the circuit configuration.

If using a 100/200-VAC 8-point Output Module, connect a fuse, which complies with
the load specifications, in series with the load.

A protective fuse does not built into the following 100/200-VAC 8-point Output
Modules. If a fuse is not connected, fire or damage to the devices or output cir-
cuits may occur if the load is short-circuited or the circuit overloaded.

Insulation Resistance

100 M

Ω min. at room temperature and humidity between input termi-

nals and ground
(measured with a 500-VDC test voltage megohmmeter).

External Power Supply

100/200 VAC supplied to drive loads

Derating Conditions

None

Internal Current Consumption

50 mA max. at 5 VDC (with all points ON)

Maximum Heating Value

9.0 W

Hot Swapping
(Removal/insertion under power)

Permitted

Approx. Mass

300 g

External Dimensions

40.3

×130×103.9 mm (W×H×D)

Item

Specifications

Output 1

Output 8

100/200 VAC

100/200 VAC

Output signal
indicator

From CPU

Phototriac

Internal circuits

CAUTION

Advertising