background image

4.1 Analog Input Specifications

4-9

4

2) Input Characteristics

The following diagram show the input characteristics.

Note: Input values exceeding the range of 0.00 V to 10.12 V will be

clamped at 0 or 4048.

Analog Input Value

Input Register Value

≤0.00 V

0000

2.50 V

1000

5.00 V

2000

7.50 V

3000

10.00 V

4000

≥10.12 V

4048

Input register value

Analog input value (V)

0-4000 mode