3 Digital I/O Specifications

3.2.1 100/200-VAC 8-point Output Module

3-26

3) The following diagram shows an example of terminal connections.

If using a 100/200-VAC 8-point Output Module, connect a fuse, which complies with
the load specifications, in series with the load.

A protective fuse does not built into the following 100/200-VAC 8-point Output
Modules. If a fuse is not connected, fire or damage to the devices or output cir-
cuits may occur if the load is short-circuited or the circuit overloaded.

Note: (1) Crimp Terminals

Use M3 terminals for crimping to the terminal block.

(2) Recommended Wires

Use wires of 1.3mm

2

(AWG16) to 0.5mm

2

(AWG20) to connect to the terminal

block.

Output 1

ACIN 1

Output 2

ACIN 2

Output 3

ACIN 3

Output 4

ACIN 4

Not
connected

Not connected

Output 5

ACIN 5

Output 6

ACIN 6

Output 7

ACIN 7

Output 8

ACIN 8

Loads

Fuses

100/200 VAC

Not connected

Loads

Fuses

100/200 VAC

100/200 VAC

100/200 VAC

100/200 VAC

100/200 VAC

100/200 VAC

100/200 VAC

Not
connected

EXAMPLE