3 Digital I/O Specifications
3.2.1 100/200-VAC 8-point Output Module
3-26
3) The following diagram shows an example of terminal connections.
If using a 100/200-VAC 8-point Output Module, connect a fuse, which complies with
the load specifications, in series with the load.
A protective fuse does not built into the following 100/200-VAC 8-point Output
Modules. If a fuse is not connected, fire or damage to the devices or output cir-
cuits may occur if the load is short-circuited or the circuit overloaded.
Note: (1) Crimp Terminals
Use M3 terminals for crimping to the terminal block.
(2) Recommended Wires
Use wires of 1.3mm
2
(AWG16) to 0.5mm
2
(AWG20) to connect to the terminal
block.
Output 1
ACIN 1
Output 2
ACIN 2
Output 3
ACIN 3
Output 4
ACIN 4
Not
connected
Not connected
Output 5
ACIN 5
Output 6
ACIN 6
Output 7
ACIN 7
Output 8
ACIN 8
Loads
Fuses
100/200 VAC
Not connected
Loads
Fuses
100/200 VAC
100/200 VAC
100/200 VAC
100/200 VAC
100/200 VAC
100/200 VAC
100/200 VAC
Not
connected
EXAMPLE
CAUTION