Yaskawa 120 Series I/O Modules User Manual

Page 296

Advertising
background image

8.1 EN Standard Compliant I/O Modules

8-9

8

3) 100- to 120-VAC or 200- to 240-VAC 16-point Output Modules

Table 8.4 Specifications of 100- to 120-VAC or 200- to 240-VAC 16-point Output Modules

Item

Specifications

Name

100- to 120-VAC or 200- to 240-VAC 16-point Output Module

Model Name

ACOUT-16P

Model No.

JAMSC-120DAO84309 (EN standard)

Rated Voltage

100 to 120 VAC or 200 to 240 VAC

Allowable Voltage Range

80 to 264 VAC

Rated Frequency

50/60 Hz

Allowable Frequency Range

47 to 63 Hz

Maximum Load Current

0.6 A rms/point, 2.4 A/common

Output Voltage Drop

1.0 V rms

Output Delay Times

OFF to ON: 5ms max.
ON to OFF: 1/2 cycle + 5 ms max.

OFF Leakage Current

3 mA max. at 240 VAC, 50 Hz

Minimum Load Current

7 mA rms

Output Type

Triac outputs

Number of Commons

2

Number of Outputs per Common

8 points/common

Output Power Supply per Common

Connect power supplies of the same phases to the common 1 and
common 2.

External Connections

Removable terminal block with M3 screw terminals.

Output Protection Type

Unprotected outputs (according to IEC 1131-2)

Built-in Fuse

Two (one per common) 5A-fuses
(Burnout time: 2 min max. at 200% of rated current)

Surge Suppressor

Varistor

Other Output Protections

None

Number of Outputs

16

Output Signal Indication

Indicator for each point; lit when the output is ON.
Status saved in internal logic

Status Indication

ACTIVE: Lit during output processing
F : Lit when a fuse is blown out or the output power supply is discon-

nected.

Insulation Method

Phototriac

Dielectric Strength

1,500 VAC for 1 min. or 1,800 VAC for 1 s between output terminals
and internal circuits and between all output commons

Insulation Resistance

100 M

Ω min. at room temperature and humidity between output ter-

minals and ground (measure by a 500-VDC test voltage megohm-
meter)

External Power Supply

100 to 120 VAC or 200 to 240 VAC to drive loads

Derating Conditions

None

Internal Current Consumption

300 mA max. at 5 VDC (with all points ON)

Hot Swapping
(Removal/insertion under power)

Permitted

Maximum Heating Value

5.5W

Approximate Mass

300g

External Dimensions

40.3

×130×103.9 mm (W×H×D)