2 register output specifications, 1 register output modules – Yaskawa 120 Series I/O Modules User Manual

Page 204

Advertising
background image

5 Register I/O Specifications

5.2.1 Register Output Modules

5-6

5.2

Register Output Specifications

5.2.1 Register Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-6

5.2.1

Register Output Modules

1) Performance Specifications

This section describes performance specifications, circuit configuration, external
connections, and appearance of the 120-series Register Output Modules.

Item

Specifications

Name

Register Output Module

Model Name

REGISTER-OUT

Model No.

JAMSC-120RDO34410

Output Circuit

s

Rated Voltage

12/24 VDC

Allowable Voltage Range

10.2 to 30.0 VDC

Output Form

Sinking output

Maximum Load Current

Data output circuit: 100 mA per point, 800 mA per 16 points
Select output circuit: 100 mA per point

Output Voltage Drop

1.5V (0.1A) max.

Output Delay Time

OFF to ON: 1 ms max.
ON to OFF: 1 ms max.

OFF Leakage Current

1 mA max. (24 VDC)

Output Type

Transistor output

Output Protection Type

Data output circuit: Protected output (according to JIS B 3502)
Select output circuit: Unprotected output

(according to JIS B 3502)

Built-in Fuse

One 1-A fuse
(Blowout time: Two minute max. at 200 % of rated current)

Surge suppressor

None

Other Output Protections

None

Number of Outputs

Data output circuit: 16 points
Select output circuit: 16 points

Output Signal Indication

None

External Connections

40-pin connector: one piece
Connector type: FCN-365P040 (made by Fujitsu Ltd.)

Status Indication

R: Lights while the Module is operating normally.
ACTIVE: Lights during output processing
F: Lights when the fuse is blown out or the output power supply

is disconnected.

Insulation Method

Photocoupler

Dielectric Strength

1,500 VAC for 1 min or 1,800 VAC for 1 s between the output
terminals (connected together) and the internal circuits.

Insulation Resistance

100 M

Ω min. at room temperature and humidity between the

output terminals and the ground (measured with a 500 VDC
test voltage megohmmeter).

External Power Supply

12/24 VDC supplied to drive loads

Derating Conditions

None

Internal Current Consumption

400 mA max. at 5 VDC

Advertising