3.2 Digital Output Module Specifications
3-37
3
2) The following diagram shows the circuit configuration.
If using a 12/24-VDC 16-point Output Module (sinking), connect a fuse, which
complies with the load specifications, in series with the load.
A protective fuse built into the following 12/24-VDC 16-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.
Output 1
Output 8
-Common 1
Output 9
Output 16
- Common 2
12/24 VDC
12/24 VDC
Output signal
indicator
From CPU
Photocoupler
+ Common 1
+ Common
Loads
Loads
Fuse
Blown fuse
Power not
connected
indicator
Blown fuse
detection circuit
Internal circuits
CAUTION