3 Digital I/O Specifications

3.2.3 12/24-VDC 8-point Output Module

3-34

3) The following diagram shows an example of terminal connections.

If using a 12/24-VDC 8-point Output Module, connect a fuse, which complies with the
load specifications, in series with the load.

A protective fuse built into the following 12/24-VDC 8-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.

Note: (1) Crimp Terminals

Use M3 crimp terminals for the terminal block.

(2) Recommended Wires

Use wires of 0.8 mm

2

(AWG18) to 0.2 mm

2

(AWG24) to connect to the terminal

block.

(3) A blown-fuse detection circuit is not built into the circuit. If no output current

flows while the output signal indicator is lit under the rated voltage, the built-in
fuse may be blown. The built-in fuse must be replaced by a Yaskawa service
representative.

Loads

Loads

Output 1A

Output 1B

Output 2A

Output 2B

Output 3A

Output 3B

Output 4A

Output 4B

Not
connected

Not connected

Output 5A

Output 5B

Output 6A

Output 6B

Output 7A

Output 7B

Output 8A

Output 8B

Not connected

Sinking connection

Sourcing connection

12/24 VDC

12/24 VDC

12/24 VDC

12/24 VDC

12/24 VDC

12/24 VDC

12/24 VDC

12/24 VDC

Not
connected

EXAMPLE

CAUTION