3 12/24-vdc 8-point output module – Yaskawa 120 Series I/O Modules User Manual

Page 62

Advertising
background image

3 Digital I/O Specifications

3.2.3 12/24-VDC 8-point Output Module

3-32

3.2.3

12/24-VDC 8-point Output Module

1) Performance Specifications

Item

Specifications

Name

12/24-VDC 8-point Output Module

Model Name

DC24OUT-8P

Model No.

JAMSC-120DDO33000

Rated Voltage

12/24 VDC

Allowable Voltage Range

10.2 to 30.0 VDC

Output Form

Sourcing or sinking

Maximum Load Current

2.0 A/point

Output Voltage Drop

0.1 V max (2.0 A)

Output Delay Times

OFF to ON: 3 ms max.
ON to OFF: 5 ms max.

OFF Leakage Current

1 mA max. at 24 VDC

Output Type

Transistor (FET) outputs

Number of Commons

8 (Each output circuit is independent.)

External Connections

Removable terminal block with M3 screw terminals

Output Protection Type

Protected outputs (according to JIS B3502)

Built-in Fuse

Eight, 3.5-A fuses (one per circuit)
(Burnout time: 1 s max. at 200% of rated current)

Surge Suppressor

Zener diode

Other Output Protection

None

Number of Outputs

8

Output Signal Indication

Indicator for each point; lit when the output is ON.
Status saved in internal logic.

Status Indication

ACTIVE: Lights during output processing.

Insulation Method

Photocoupler

Dielectric Strength

1,500 VAC for 1 min or 1,800 VAC for 1 s between output
terminals and internal circuits

Insulation Resistance

100 M

Ω min. at room temperature and humidity between

output terminals (connected together)

and ground

(measured with a 500-VDC test voltage megohmmeter).

External Power Supply

12/24 VDC supplied to drive loads

Derating Conditions

None

Internal Current Consumption

220 mA max. at 5 VDC (with all points ON)

Maximum Heating Value

1.6 W

Hot Swapping
(Removal/insertion under power)

Permitted

Approximate Mass

250 g

External Dimensions

40.3

×130×103.9 mm (W×H×D)

Advertising