7 Maintenance

7.1.2 Built-in Fuses

7-4

3) DC 16-point Output Module

a) The fuse inside a DC 16-point Output Module is not to protect the output circuit. The

fuse prevents the Module from damage that may occur in the following cases:

• External causes: For example, when over-voltage is applied to the power termi-

nals for driving load of the DC 16-point Output Module.

• Internal causes: For example, when foreign matter such as chips are present in

the DC 16-point Output Module, and thereby short-circuiting the
internal circuits.

b) When the built-in fuses are blown out, the indicator lamp “F” of the DC 16-point Out-

put Module is lit. If the fuses are blown out, eliminate the cause and replace the
fuse.

The fuses built in the DC 16-point Output Modules can be replaced by users.

4) DC 32-point Output Modules

Do not replace the built-in fuses of the DC 32-point Output Modules.

If the built-in fuses are replaced by anyone other than a Yaskawa-approved
technician, a failure or malfunction may occur in the DC 32-point Output Mod-
ules, and the guarantee is void.

a) The fuse inside a DC 32-point Output Module is not to protect the output circuit. The

fuse prevents the Module from damage that may occur in the following cases:

• External causes: For example, when over-voltage is applied to the power termi-

nals for driving load of the DC 32-point Output Module.

• Internal causes: For example, when foreign matter such as chips are present in

the DC 32-point Output Module, and thereby short-circuiting the
internal circuits.

b) When the built-in fuses are blown out, the indicator lamp “F” of the DC 32-point Out-

put Module is lit. If the fuses are blown out, eliminate the cause and replace the
Module with a spare DC 32-point Output Module.