Yaskawa 120 Series I/O Modules User Manual

Page 175

Advertising
background image

4 Analog I/O Specifications

4.2.2 Analog Output Modules (0 to 10 V, 2 channels) (0 to 5 V, 2 channels)

4-28

4) The following diagram shows an example for terminal connections.

Note: (1) Isolation between Output Channels

All the channels of the output circuit are isolated each other.

(2) Recommended Cables

Use shielded twisted-pair wires of 1.3 mm

2

(AWG16) to 0.5 mm

2

(AWG20) to

connect to the terminal block.

(3) One-point Shield Connection

As a rule, connect the shield at one point on the load side. However, better out-
put characteristics may be obtained by connecting it at one point on the Module
side rather than on the load side, so consider which way is better depending on
the actual situation. An incorrect connection will make input signal unstable and
cause malfunction.

(4) Grounding the Module

The FG terminal of the Module is connected to the Mounting Base via the Mod-
ule. When grounding on the Module side, use the FG terminal. The “Not con-
nected” terminals are not connected inside the Module. Use them as relay
terminals.

(5) Crimp Terminals

Use M3 terminals for crimping to the terminal block.

(6) Unconnected Terminals

Terminals 1 to 5, 7, 9 to 13, 15, 17, 18 and 20 are not connected.

Not connected

Not connected

Not connected

Shielded twisted-pair wire

External device

External device

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

Not connected

0 to 10 V

0 to 10 V

Shielded twisted-pair wire

CH2 -

CH2 +

CH1 -

CH1 +

EXAMPLE

Advertising