3 Digital I/O Specifications

3.2.6 12/24-VDC 32-point Output Module

3-46

3) The following diagram shows an example of terminal connections.

Although a 0.3 A load can be connected to each output point of 12/24-VDC 32-point
Output Module, the total load must be 0.4 A or less for each of the four output points
shown in the shaded area. Keep the load distribution within the 0.4 A limit.

If this limit is exceeded, damage may occur to the output circuit.

If using a 12/24-VDC 32-point Output Module, connect a fuse, which complies with
the load specifications, in series with the load.

A protective fuse built into the following 12/24-VDC 32-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.