4.3 I/O Allocation

4-39

4

4.3.2

Analog Output Modules

1) I/O Allocation

The relationship between I/O signals and I/O references must be defined so that the
CPU Module can input signals from input devices and output signals to output
devices. The following settings are necessary to define this relationship for Analog
Output Modules.

• Module Type

• I/O Reference Numbers

• I/O Data Format

Setting these items is performed in a process called I/O allocation. I/O allocation is
performed using the MEMOSOFT and the settings are recorded in the I/O allocation
tables stored in memory in the CPU Module.

Refer to the following manuals for specific setting procedures.

• MEOCON GL120, GL130 MEMOSOFT for P120 Programming Panel User’s

Manual (Manual No. SIEZ-C825-60.7), Chapter 7 Setting System Configuration.

• MEMOCON GL120, GL130 MEMOSOFT for DOS User’s Manual (Manual No.

SIEZ-C825-60.10), Chapter 7 Setting System Configuration.

• MEMOCON GL120, GL130 MEMOSOFT for Windows User’s Manual (Manual

No. SIEZ-C825-60.25), Chapter 6 Setting the Module Configuration.

a) Module Type Setting

The type of Output Module mounted in the slot is set as the Module type. Only the
last 11 alphanumeric characters of the model number are necessary. For example
120AVO01000 is the Module type for the JAMSC-120AVO01000.

b) I/O Reference Number Setting

(1) The leading I/O reference number used by the Output Module is set.

(2) Two continuous output registers are allocated. The I/O reference numbers and

points that can be allocated are listed in the following table.

(3) The two output registers that are allocated are used as shown in the following

table. Here, n is between 0 and 510.

Type of Input

References for I/O Allocation

Number of

Registers

CPU10, CPU20, CPU21

CPU30, CPU35

Output registers 400001 to 400512

400001 to 400512

2 registers

Output Register

Reference Number

Application

400001 + n

Analog output signal for channel 1

400002 + n

Analog output signal for channel 2

Advertising