6 Installation and Wiring

6.2.5 Grounding

6-28

6.2.5

Grounding

1) Grounding the Analog Input Modules

Do not allow foreign matter such as cable chips in the Modules or Mounting Bases.

Foreign matter in the Modules or Mounting Bases may cause fire, failures, and/
or malfunctions.

Ground the ground terminal of the Analog Input Module to a resistance of 100

Ω max.

Not grounding the ground terminal may result in malfunction of the GL120 and
GL130.

a) Connect the ground terminal (FG) and the ground terminal of the control panel (E)

with 1.5 mm

2

(AWG16) to 2.5 mm

2

(AWG13) cable (in-panel ground cable.)

b) If more than one Analog Input Module is used, do not cross-wire between the ground

terminals. Connect the ground terminal of each Analog Input Module to the ground
terminal of the control panel separately, as shown in the following figure.

c) M3 Phillips screws are used on the field wiring terminals. Accordingly, use crimp ter-

minals for M3 Phillips screws for the in-panel ground cable ends.

Fig. 6.6 Grounding for Analog Input Module

CAUTION

CAUTION

AC1

AC2

ACG

FG

CH1+

CH1-

Shield 1

FG

In-panel ground cable
(1.5 to 2.5 mm

2

)

Control panel

Ground terminal (E)

In-panel ground cable
(1.5 to 2.5 mm

2

)

Outside-panel ground
cable (8 mm

2

or lager)

Field wiring terminal of

Power Supply Module

Ground pole

(with a resistance of 100

Ω max.)

Field wiring terminal of
Analog Input Module