2 digital output module specifications, 1 100/200-vac 8-point output module – Yaskawa 120 Series I/O Modules User Manual

Page 54

Advertising
background image

3 Digital I/O Specifications

3.2.1 100/200-VAC 8-point Output Module

3-24

3.2

Digital Output Module Specifications

3.2.1 100/200-VAC 8-point Output Module - - - - - - - - - - - - - - - - - - - - - - - 3-24
3.2.2 100/200-VAC 16-point Output Module - - - - - - - - - - - - - - - - - - - - - - 3-28
3.2.3 12/24-VDC 8-point Output Module - - - - - - - - - - - - - - - - - - - - - - - - 3-32
3.2.4 12/24-VDC 16-point Output Module (Sinking) - - - - - - - - - - - - - - - - 3-36
3.2.5 12/24-VDC 16-point Output Module (Sourcing) - - - - - - - - - - - - - - - 3-40
3.2.6 12/24-VDC 32-point Output Module - - - - - - - - - - - - - - - - - - - - - - - 3-44
3.2.7 12/24-VDC 64-point Output Module - - - - - - - - - - - - - - - - - - - - - - - 3-49
3.2.8 Relay Contact 16-point Output Module - - - - - - - - - - - - - - - - - - - - - 3-55

3.2.1

100/200-VAC 8-point Output Module

1) Performance Specifications

This section describes the performance specifications, circuit configuration, external
connections, and external appearance of the 120-series Digital Output Modules.

Item

Specifications

Name

100/200-VAC 8-point Output Module

Model Name

ACOUT-8P

Model No.

JAMSC-120DAO83000

Rated Voltage

100/200 VAC

Allowable Voltage Range

80 to 264 VAC

Rated Frequency

50/60 Hz

Allowable Frequency Range

47 to 63 Hz

Maximum Load Current

1.0 Arms/point

Output Voltage Drop

1.0 Vrms

Output Delay Times

OFF to ON: 5 ms max.
ON to OFF: 1/2 cycle + 5 ms max.

OFF Leakage Current

3 mA max. at 240 VAC, 50 Hz

Minimum Load Current

10 mArms

Output Type

Triac outputs

Number of Commons

8 (Each output circuit is independent.)

Output Power Supply
per Common

Possible to connect different power supply phases to the commons.

External Connections

Removable terminal block with M3 screw terminals

Output Protection Type

Unprotected outputs (according to JIS B3502)

Built-in Fuse

None

Surge Suppressor

Varistor

Other Output Protection

None

Number of Outputs

8

Output Signal Indication

Indicator for each point; lit when the output is ON.
Status saved in internal logic.

Status Indication

ACTIVE: Lights during input processing.

Insulation Method

Phototriac

Dielectric Strength

1,500 VAC for 1 min or 1,800 VAC for 1 s between output terminals and
internal circuits and between all output circuits.

Advertising