3 Digital I/O Specifications

3.1.1 100-VAC 16-point Input Module

3-2

3.1

Digital Input Module specifications

3.1.1 100-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-2
3.1.2 200-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-6
3.1.3 12/24-VDC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-10
3.1.4 12/24-VDC 32-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-14
3.1.5 12/24-VDC 64-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-18

3.1.1

100-VAC 16-point Input Module

1) Performance Specifications

This section describes the performance specifications, circuit configuration, external
connections, and the external appearance of the 120-series Digital Input Modules.

Item

Specifications

Name

100-VAC 16-point Input Module

Model Name

AC100IN-16P

Model No.

JAMSC-120DAI54300

Rated Voltage

100 VAC

Maximum Allowable Voltage

132 VAC

Rated Frequency

50/60 Hz

Allowable Frequency Range

47 to 63 Hz

Inrush Current

160 mA

Rated Current

7 mA (at 100 VAC, 50 Hz)

Input Impedance

14.3 k

Ω (at 100 VAC, 50 Hz)

12.5 k

Ω (at 100 VAC, 50 Hz)

Standard Operating Ranges

ON voltage range: 74 to 132 VAC
OFF voltage range: 30 VAC max.

Input Type

AC type2 (according to JIS B3502)

Input Delay Times

OFF to ON: 20 ms max.
ON to OFF: 35 ms max.

Number of common

2

Number of Inputs per Common

8 points/common

Input Power Supply per Common

Connect power supplies of the same phase to the Common 1 and
Common 2.

External Connections

Removable terminal block with M3 screw terminals

Number of Inputs

16

Input Signal Indication

Indicator for each point; lit when the input is ON.
Status saved in internal logic.

Status Indication

ACTIVE: Lights during input processing

Insulation Method

Photocoupler

Dielectric Strength

1,500 VAC for 1 min or 1,800 VAC for 1 s between input terminals and
internal circuits and between all input commons.

Insulation Resistance

100 M

Ω min. at room temperature and humidity between input termi-

nals and ground
(measured with a 500-VDC test voltage megohmmeter).

External Power Supply

100 VAC supplied to signals

Derating Conditions

None

Internal Current Consumption

90 mA max. at 5 VDC (with all points ON)