3 Digital I/O Specifications

3.3.4 W0301 Cables (Model No. JZMSZ-120W0301-††)

3-68

3.3.4

W0301 Cables (Model No. JZMSZ-120W0301-††)

1) Use

(1) This Cable is used to connect external devices to the Modules listed below.

(a) 12/24VDC 32-point Input Module (Model No. JAMSC-120DDI35400)

(b) 12/24VDC 32-point Output Module (Model No. JAMSC-120DDO35410)

(2) The end of the Cable on the external device is fitted with a connector.

Use the Cable in combination with a 32-point I/O connector Terminal Block.
See 3.3.5 32-point I/O Connector Terminal Block for information about the 32-
point I/O connector Terminal Block.

2) Specifications

The following table shows specifications of W0301 Cables.

3) Appearance

The following illustration shows the appearance of a W0301 Cable.

Table 3.5 Specifications of W0301 Cable

Item

Specifications

Model Name

W0301-01

W0301-03

W0301-05

Model No.

JZMSZ-120W0301-01 JZMSZ-120W0301-03

JZMSZ-120W0301-05

Length L

1.0 m

3.0 m

5.0 m

Cable
Specifications

Shielded cable, 40 cores, equivalent to UL20276, AWG28 (0.08 mm

2

)

Cable
Termination

Module
side

Connector: Connector 10140–6000EL (3M)

Shell 10640-5500-008 (3M)
Screw 3342-26 (3M)
Latch 10600-L0F0-8 (3M)

External
device
side

Connector fitted: FCN-361J040-AU + FCN-360C040-E
(made by Fujitsu Ltd.).

Insulation
Resistance

100 M

Ω min. at room temperature and humidity between core wires

(connected together) and shielding wire, and between core wires
(measured with a 500-VDC test voltage megohmmeter).

Connector 1 (Module side)

Model name

Connector 2 (external device side)

Shielded cable

Advertising