1 analog input specifications, 1 analog input modules (±10 v, 4 channels), 1 analog input modules ( ± 10 v, 4 channels) – Yaskawa 120 Series I/O Modules User Manual

Page 149

Advertising
background image

4 Analog I/O Specifications

4.1.1 Analog Input Modules (

±10 V, 4 channels)

4-2

4.1

Analog Input Specifications

4.1.1 Analog Input Modules (

±10 V, 4 channels) - - - - - - - - - - - - - - - - - - - - 4-2

4.1.2 Analog Input Modules (0 to 10 V, 4 channels) - - - - - - - - - - - - - - - - - 4-8
4.1.3 Analog Input Modules (4 to 20-mA, 4 channels) - - - - - - - - - - - - - - - 4-14

4.1.1

Analog Input Modules (

±10 V, 4 channels)

1) Performance Specifications

This section describes performance specifications, circuit configuration, external
connections, and appearance of the 120-series Analog Input Modules.

Item

Specification

Name

Analog Input Module (

±10 V, 4 channels)

Model Name

A/D-VOL-4CH

Model No.

JAMSC-120AVI02000

Input Signal Range

-10 to 10 V

Special Input

None

Number of Input Channels

4 channels, isolated in common

Input Impedance

1 M

Ω min

Maximum Allowable Overload

-25 to 25 V

Digital Resolution

12 bits

Data Format

1) Two modes available, set by allocation

0-4000 mode/

±2000 mode

2) Range of numerical values for each mode is as follows:

0-4000 mode: Binary, 0 to +4000
±2000 mode: 2’s complement, -2000 to +2000

Errors

±0.5% F.S. (25 °C)
±1.0% F.S. (0 to 60 °C)

Input Delay Time

4 ms max.

Sampling Interval

Input data is renewed for every scan by CPU

Input Filter Characteristics

3 ms max.

Number of Allocated Words

5 words/Module

Maintenance/Diagnosis Functions

Watchdog timer (timeout: 262 ms)

External Connections

Removable terminal block with M3 screw terminals

Status Indication

RDY: Lights when Module is normal
ACT: Lights during input processing
ERR: Lights when overrange is detected
CH1 to CH4: The corresponding LED is lit when overrange is

detected for the channel.*

Insulation Method

Photocoupler

Dielectric Strength

1,500 VAC for one minute between input terminals (con-
nected together) and internal circuits
No insulation between input channels

Insulation Resistance

100 M

Ω min. at room temperature and humidity between

input terminals and ground (measured with a 500-VDC test
voltage megohmmeter).

External Power Supply

Not needed

Internal Current Consumption

450 mA max. at 5 VDC

Advertising