8 relay contact 16-point output module – Yaskawa 120 Series I/O Modules User Manual

Page 85

Advertising
background image

3.2 Digital Output Module Specifications

3-55

3

3.2.8

Relay Contact 16-point Output Module

1) Performance Specifications

Item

Specifications

Name

Relay Contact 16-point Output Module

Model Name

RELAY-16P

Model No.

JAMSC-120DRA84300

Co

nt

a

ct S

pecificatio

ns

Rated Voltage/Current

200 VAC, 1 A, resistive load
24 VDC, 1 A, resistive load

Maximum Load Power

750 VA (AC loads)
90W (DC loads)

Maximum Load Voltage

264 VAC/125 VDC

Minimum Load
Voltage/Current

100 mVDC, 0.1 mA

Contact Resistance

100 m

Ω max.

Contact Life

Electrical

3 A at 30 VDC, resistive load: 100,000 operations min.

1 A at 30 VDC, resistive load:

τ = 7 ms:

τ = 40 ms:

300,000 operations min.
150,000 operations min.
40,000 operations min.

1 A at 120 VAC, cos

φ = 1.0:

cos

φ = 0.4:

400,000 operations min.
250,000 operations min.

1 A at 240 VAC, cos

φ = 1.0:

cos

φ = 0.4:

300,000 operations min.
200,000 operations min.

Mechanical

20 million operations min.

Output Delay Times

OFF to ON: 10 ms max.
ON to OFF: 15 ms max.

Output Type

Relay contact outputs

Number of Commons

2

Number of Outputs per Common

8 points/common

Output Power Supply per
Common

Connect power supplies of the same phase to the Common 1
and Common 2 for 100/200VAC.

External Connections

Removable terminal block with M3 screw terminals

Output Protection Type

Unprotected outputs (according to JIS B3502)

Built-in Fuse

None

Surge Suppressor

None

Other Output Protection

None

Number of Outputs

16

Output Signal Indication

Indicator for each point; lit when the output is ON.
Status saved in internal logic.

Status Indication

ACTIVE: Lights during output processing

Insulation Method

Relay

Dielectric Strength

1,500 VAC for 1 min or 1,800 VAC for 1 s between output termi-
nals and internal circuits and between all output commons

Insulation Resistance

100 M

Ω min. at room temperature and humidity between output

terminals and ground (measured with a 500-VDC test voltage
megohmmeter).

External Power Supply

100/200 VAC or 24 VDC supplied to drive loads

Derating Conditions

None

Internal Current Consumption

610 mA max. at 5 VDC (with all points ON)

Advertising