Yaskawa 120 Series I/O Modules User Manual

Page 166

Advertising
background image

4.1 Analog Input Specifications

4-19

4

6) External Appearance

LED

Color

State

Indication when ON

RDY

Green

Lit

Module is normal.

Flashing

Initial check error has occurred.

Not lit

WDT timeout error has occurred.

ACT

Green

Lit

Module is processing I/O.

Not lit

CPU Module is in the STOP state or I/O pro-
cessing error has occurred.

ERR

Red

Lit

Overrange is detected at one of the channels,
CH1 to CH4.

Flashing

Parameter check sum error has occurred.

Not lit

Module is normal.

CH 1 to CH 4 Green

Lit

Input signal of indicated channel exceeds the
input signal range shown below.

• 20.48 mA < Input signal
• Input signal < 2.0 mA

Flashing

Input signal of indicated channel exceeds the
input signal range shown below.

• 20.0 mA < Input signal < 20.48 mA.
• 2.0 mA < Input signal < 4.0 mA.

Removable terminal block
for field connections

Hinged terminal cover

Signal label insert

Color code
(light green)

LED area

Module mounting screw
(Use a M4 Phillips screwdriver.)

Module description (120ACI02000)

External wiring terminal
(Use a M3 Phillips screwdriver.)

Terminal block mounting screw
(Use a M3 Phillips screwdriver.)

LED Area

120 ACI 021 00

ACT
CH1
CH2
CH3
CH4

ERR

RDY